New boiler in a hard water area: the 200 ppm rule
If a combination boiler or water heater is being fitted in England and the water is harder than 200 ppm, the building regulations guidance expects limescale protection on it. Below is the wording, a check for any postcode, and what counts as protection.
Is this postcode over 200 ppm?
Water company hardness readings for 2,312 UK postcode districts.
According to TapWater.uk, 976 of 2,043 UK postcode districts with a hardness reading (48%) are over the 200 ppm line that Approved Document L uses to define a hard water area. In those districts the guidance for England asks for limescale protection on new combination boilers and water heaters.
What the document says
The rule sits in Approved Document L, Volume 1: Dwellings (2021 edition incorporating 2023 amendments), in the section on commissioning hot water systems. Paragraph 8.8 reads:
“In hard water areas, suitable measures should be taken to treat the feed water to water heaters and the hot water circuit of combination boilers to reduce limescale accumulation.”
And the key terms at the back say what a hard water area is:
“For the purposes of this approved document, hard water is water that has a total water hardness of greater than 200ppm of CaCO3.”
Two things follow. The line is over 200, so a reading of exactly 200 is not caught. And an approved document is guidance, not the law itself: following it is the usual way to show building control that the work meets the Building Regulations. It applies in England. Approved Document L on gov.uk
What 200 ppm means
Parts per million of calcium carbonate is the same number as milligrams per litre, which is how water companies publish hardness. On the scale most of them use, water is hard from 180 mg/L and very hard from 250, so the building regulations line falls inside the hard band. A district at 190 is hard by the water company’s description and still under the line.
How much of the country is over the line
Of the 2,043 postcode districts where we hold a water company reading, 976 are over 200 ppm, about 48 in every 100. These are the postcode areas with the most districts over the line.
| Postcode area | Districts over the line | Median, ppm |
|---|---|---|
| Norwich (NR) | 35 of 35 | 348 |
| Bristol (BS) | 33 of 37 | 223 |
| Ipswich (IP) | 32 of 32 | 390 |
| Peterborough (PE) | 32 of 34 | 297 |
| Doncaster (DN) | 32 of 32 | 293 |
| Reading (RG) | 29 of 29 | 297 |
| South East London (SE) | 28 of 28 | 265 |
| South West London (SW) | 27 of 27 | 263 |
| Milton Keynes (MK) | 26 of 26 | 274 |
| Oxford (OX) | 25 of 25 | 264 |
| Chelmsford (CM) | 24 of 24 | 314 |
| Hemel Hempstead (HP) | 24 of 24 | 292 |
| Brighton (BN) | 24 of 29 | 253 |
| York (YO) | 23 of 28 | 265 |
| Guildford (GU) | 23 of 36 | 264 |
Counted from readings only; districts where we hold just a postcode-area estimate are left out. Thames Water reports by supply zone, so its districts take the average of the zones they fall in. In inner London (E1 to E9, N1 to N9, W2 to W9) Thames's checker cannot name the zone, and we use the zones of the districts around them. See the whole country on the hardness map
What counts as a suitable measure
The document names no product. In practice there are two routes, and they do different jobs.
A scale reducer on the cold feed to the boiler
A small inline unit fitted on the pipe that feeds the boiler’s hot water side. Some dose a trace of polyphosphate to hold the minerals in the water; others are electrolytic or magnetic. It protects the boiler and nothing else: the water stays as hard as it was, so kettles, taps and shower screens scale up as before. What the evidence says about each kind is in our guide to salt-free devices.
A water softener on the rising main
Takes the hardness out of all the water entering the house, so the boiler, the cylinder and every tap are covered at once, and the reading in ppm falls. Supplied and fitted, one typically costs £1,195 to £2,900. It is the only one of the two that removes limescale from the rest of the home. Check the boiler maker’s instructions too, because some set conditions on softened water in the heating circuit.
If you are having a boiler fitted
Check the postcode above. If it is over the line, ask the installer what they are fitting for scale and where, and ask for it to be written on the commissioning record. The approved document notes that the Benchmark Commissioning Checklist can be used to show the system was commissioned properly, so that is the natural place for it.
If you fit boilers
The check above works on a phone and takes the first half of the postcode. The figures are the water companies’ own, with a note wherever a district has no reading of its own. If you want the hardness for every job in your own quoting or survey software, it is available for every district as a file or over an API. Water data for business
Over the line? Price a softener while the plumber is there
A softener covers the boiler and the rest of the house in one go. Supplied and fitted, one typically costs £1,195 to £2,900. Request free quotes from installers who cover your postcode.
A fitted softener typically costs £1,195 to £2,900. Prices by brand, with sources. Request a free assessment and we'll come back to you with local installer options for your area.
100%
free, no obligation
shared only with your consent
Frequently asked questions
Is a scale reducer a legal requirement on a new boiler?
Not by name. Approved Document L, the guidance on meeting the energy part of the Building Regulations in England, says that in hard water areas suitable measures should be taken to treat the feed water to water heaters and the hot water circuit of combination boilers. It defines a hard water area as over 200 ppm. Following the approved document is the usual way to show the work complies, and a scale reducer on the cold feed is the measure most installers use.
What counts as a hard water area in the building regulations?
Water with a total hardness greater than 200 ppm of calcium carbonate. That is the definition in the key terms of Approved Document L, Volume 1: Dwellings. 200 ppm is the same as 200 mg/L, the unit water companies publish.
Does a water softener count as a suitable measure?
The document does not list products. A softener takes the hardness out of all the water entering the house, including the feed to the boiler, which is what the paragraph asks for. Check the boiler maker's installation instructions as well, because some set their own conditions on softened water in the heating circuit.
How do I find the water hardness for a property in ppm?
Enter the postcode in the check on this page. The figure is the water company's own reading in mg/L of calcium carbonate, which is the same number as ppm. Where a district has no reading of its own we say so and give the median for its postcode area.
Does the 200 ppm rule apply in Wales, Scotland and Northern Ireland?
This page covers Approved Document L for England. Wales, Scotland and Northern Ireland publish their own building regulations guidance, so check with building control there. The hardness figures on this page cover the whole UK.
My water is under 200 ppm. Do I still need scale protection?
The approved document does not ask for it. Hardness still varies from one supply zone to the next and through the year, so if the figure is close to the line, or the boiler maker's instructions set a lower limit, a scale reducer is a small cost against a scaled-up heat exchanger.